Reflectance Dependent Models – Analog
Philtec Model D63
Technical datasheet for the Philtec Model D63 reflectance-dependent analog fiberoptic displacement sensor. 1.6 mm spot size, 3.0 mm total operating range, and DC–20 kHz bandwidth with high resolution.
Technical datasheet for the Philtec Model D63 reflectance-dependent analog fiberoptic displacement sensor. 1.6 mm spot size, 3.0 mm total operating range, and DC–20 kHz bandwidth with high resolution.
Overview
The Philtec Model D63 is a reflectance-dependent analog fiberoptic sensor for distance, displacement, and vibration of targets larger than Ø 1.6 mm with high resolution. A standard single-channel unit includes the amplifier, the sensor tip, and a 914 mm (3 ft) fiberoptic cable. It runs on +12 to +24 VDC and provides a 0 to +5 V analog output.
Output voltage is proportional to both the tip-to-target gap and the reflectivity of the target surface. D models are used where target reflectivity stays constant, such as reciprocating or vibratory motion parallel to the sensor axis.
- Near side: steep slope before the peak. High sensitivity (100 mV/µm nominal), limited operating range (150 µm).
- Optical peak: set to 5.000 V. Zero displacement sensitivity, reflectance dependent; used as the calibration reference.
- Far side: gradual slope after the peak. Moderate sensitivity (3.2 mV/µm nominal), greater operating range (2.85 mm).
Specifications
Far side and near side
| Parameter | Far side (Metric) | Far side (Imperial) | Near side (Metric) | Near side (Imperial) |
|---|---|---|---|---|
| Total range | 2.85 mm | 0.112 in | 150 µm | 0.006 in |
| Linear range | 0.7 mm | 0.028 in | 20 µm | 0.0008 in |
| Nominal standoff | 0.5 mm | 0.021 in | 28 µm | 0.0011 in |
| Nominal sensitivity | 3.2 mV/µm | 80 mV/mil | 100 mV/µm | 2.5 mV/µin |
| Resolution, DC–200 kHz | 0.6 µm | 24 µin | 26 nm | 1.0 µin |
| Resolution, DC–20 kHz | 0.3 µm | 12 µin | 13 nm | 0.5 µin |
| Resolution, DC–100 Hz | 0.13 µm | 5 µin | 2 nm | 0.08 µin |
Tip and cable dimensions
| Feature | Metric | Imperial |
|---|---|---|
| Tip outer diameter (Ø C) | 3.18 mm | 0.125 in |
| Fiberoptic diameter | 1.6 mm | 0.063 in |
| Tip length (C) | 76.2 mm | 3 in |
| Collar length (B) | 12.7 mm | 0.5 in |
| Collar diameter (Ø B) | 6.35 mm | 0.25 in |
| Cable length (A) | 914 mm | 36 in |
| Cable diameter (Ø A) | 5.7 mm | 0.225 in |
| Cable min. bend radius | 19 mm | 0.75 in |
Electronics
| Light source | LED, 850 nm |
|---|---|
| Input voltage | +12 to +24 VDC |
| Input current | 125 mA max |
| Bandwidth | DC–20 kHz standard (3 dB down); up to 2 MHz optional |
| Isothermal drift | 0.5% |
| Amplifier temperature | 0 to 70 °C |
| Weight | 0.7 kg (1.5 lb) |
Fiberoptics and probe
| Light beam spread | 66° |
|---|---|
| Tip material | 300 series stainless steel |
| Tip epoxy outgas | 0.3% @ 200 °C; 2.4% @ 300 °C |
| Tip pressure | 15 bar |
| Tip temperature | −55 to 200 °C continuous; to 300 °C intermittent (1–2 hr) |
| Cable temperature | 10 to 107 °C |
| Cable jacket | PVC over steel monocoil |
Nominal standoff is the gap at the middle of the linear operating range. Published specifications provide nominal values only; actual production units can vary by up to ±15%.
Resolution figures represent best-case performance assuming a flat, smooth, highly reflective target, a perpendicular sensor, the gap of highest sensitivity, and a standard unconnectorized cable.
Response curves
- Linear range, ±1%: 0.27 mm to 0.92 mm (0.7 mm nominal linear range).
- Output peaks at 5.0 V around 0.15 mm, then decreases across the 3.0 mm span.
- Linear range, ±1%: 17.8 µm to 43.2 µm (20 µm nominal linear range).
- Output rises steeply from contact and levels near 5.0 V around 150 µm.
Distance from the analog output
Inside a linear range, gap change equals the change in millivolts divided by sensitivity (Distance = Δ milliVolts ÷ Sensitivity = µm). Over non-linear ranges, create a lookup table from the XY calibration points or apply a polynomial curve fit.
Questions
What target size and resolution does the Model D63 cover?
The target spot size is 1.6 mm (0.063 in), designed for targets larger than Ø 1.6 mm with high resolution. Best near-side resolution is 2 nm at DC–100 Hz, and 13 nm at the standard DC–20 kHz bandwidth.
When is the near side used instead of the far side?
Use the near side for ultra-high sensitivity (100 mV/µm nominal; 83 mV/µm typical) across a 20 µm linear range (17.8–43.2 µm typical) centered at 28 µm standoff. Use the far side for a wider 0.7 mm linear range (0.27–0.92 mm typical), 3.2 mV/µm nominal sensitivity, and 0.5 mm standoff clearance.
How is in-situ calibration performed on different target surfaces?
Adjust the tip-to-target gap until the optical peak output is reached, then use the amplifier gain control to set the peak voltage to full scale (5.000 V). Once set, the factory gap calibration chart applies directly to that target material.
Can the probe tip run hot or under pressure?
The 300-series stainless steel tip is rated from −55 °C to 200 °C continuous (and up to 300 °C intermittent for 1–2 hours) and up to 15 bar pressure. The amplifier electronics are rated 0 to 70 °C.